Generac — Testing Generator Under Load

Testing & diagnosis · Generator set / transfer switch

From a Generac owner's manual — check it applies to your exact model before use.

Applies to: John Deere 4.5 L engine, Generac 4.5L engine, Iveco/FPT 4.5L engine

Before you start

  • High voltage present at transfer switch and terminals

Procedure

  1. Verify generator OFF and all loads off
  2. Turn off utility power supply to transfer switch
  3. Manually set transfer switch to STANDBY
  4. Press MANUAL to crank/start engine and allow warm-up
  5. Set generator MLCB to ON (CLOSED)
  6. Turn on circuit breakers/loads supplied by generator
  7. Connect AC voltmeter/frequency meter across E1,E2,E3 and verify voltage near rated value; verify not overloaded with clamp amp meter
  8. Run at full rated load 20-30 minutes, listening/inspecting for abnormal operation
  9. Turn off loads, set MLCB OFF, run at no-load 2-5 minutes, then press OFF