Generac — Testing DEF

Maintenance · DEF system

From a Generac owner's manual covering: MDG150, MDG175, MDG250. Check it applies to your exact model before use.

Applies to: Generac MDG150, Generac MDG175, Generac MDG250

Before you start

  • Do not create DEF by mixing agricultural grade urea with water.

Procedure

  1. Draw a DEF sample into a clear container; DEF must be crystal clear.
  2. If cloudy or tinted, drain tank, flush with distilled water, fill with new DEF.
  3. If it passes visual and smell tests, check concentration with a refractometer.
  4. Correct concentration is 31.8–33.2% urea.
  5. If out of specification, drain, flush with distilled water, and fill with new or good DEF.

Tools required

  • JDG11594 Digital DEF Refractometer Amazon
  • JDG11684 DEF Refractometer Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 31.8–33.2% urea
  • ISO 22241-1

Full service-parts list: Generac MDG150 →, Generac MDG175 →, Generac MDG250 →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.