Generac — Test 40 - Test Oil Temperature Switch

Testing & diagnosis

From a Generac service manual covering: 4700, QuietPact 40, QuietPact 40 LP, QuietPact 40G, QuietPact 40LP. Check it applies to your exact model before use.

Applies to: Generac 4700, Generac QuietPact 40, Generac QuietPact 40 LP, Generac QuietPact 40G, Generac GH-220 engine

Procedure

  1. Remove Wire No. 85 from switch terminal and start generator to isolate the fault
  2. Remove switch and place sensing tip into oil with a thermometer
  3. Connect VOM test leads across switch terminals; should read infinity
  4. Heat oil; at approximately 305°F (151°C) switch contacts should close and meter should read continuity

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Switch closes at approximately 305°F (151°C)

Full service-parts list: Generac 4700 →, Generac QuietPact 40 →, Generac QuietPact 40 LP →, Generac QuietPact 40G →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.