Generac — Test 4 – Field Flash Alternator (Configuration A Only)

Repair & overhaul · Brushless capacitor alternator

From a Generac service manual covering: GP1800, GP1850, GP3250, GP5000, GP5500, GP6500, GP7000, GP8000. Check it applies to your exact model before use.

Applies to: Generac GP1800, Generac GP3250, Generac GP5000, Generac GP5500, Generac GP6500, Generac GP7000, Generac GP8000, Generac OHVI engine

Before you start

  • Do NOT energize the capacitor for more than 1 second at a time.
  • Do not field flash alternator more than two times in sequence.

Procedure

  1. Construct an energizing cord as shown and connect as shown.
  2. Set START-RUN-STOP switch to OFF position.
  3. Momentarily turn on the energizing cord (one second).
  4. Disconnect the energizing cord from the capacitor.
  5. Check generator produces approximately 240 VAC at main circuit breaker.

Tools required

  • energizing cord (12 AWG, momentary pushbutton switch) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • ~240 VAC at main circuit breaker

Full service-parts list: Generac GP1800 →, Generac GP3250 →, Generac GP5000 →, Generac GP5500 →, Generac GP6500 →, Generac GP7000 →, Generac GP8000 →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.