Generac QuietPact 40 — Out of Service Procedure - Removal from Service
Maintenance · Generator
For the Generac QuietPact 40, from the Generac owner's manual.
Applies to: Generac QuietPact 40, Generac GN-220 engine
Before you start
- Never store the battery on any concrete or earthen floor.
Procedure
- Start the engine and let it warm up.
- Close the fuel shutoff valve and allow the unit to shut down.
- While warm, drain the oil and refill the crankcase with SAE 10W-30 SF oil.
- Attach a tag indicating the viscosity and classification of the oil.
- Remove the spark plug, pour two or three tablespoons of oil into the opening, reinstall and tighten plug.
- Remove the battery and store in a cool, dry room on a wooden board.
- Clean and wipe the entire generator.
Full service-parts list: Generac QuietPact 40 →
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.