Generac QT 3.9L 40kW — Preparation for Start-Up

Installation · Generator set

For the Generac QT 3.9L 40kW, from the Generac owner's manual.

Applies to: Generac QT 3.9L 40kW, Generac QT Series, Generac V-type engine

Before you start

  • Ensure AUTO/OFF/MANUAL switch is in OFF position before working on the generator.

Procedure

  1. Ensure 120VAC circuit breaker to battery charger is open.
  2. Remove the fuse from the control panel (H-100/R-series: 15 Amp ATO fuse).
  3. Connect battery cables; attach negative cable last.
  4. Close 120VAC circuit breaker to the battery charger.
  5. Insert the fuse into the control panel.
  6. Move AUTO/OFF/MANUAL switch to MANUAL; engine should crank and start.
  7. Check voltage at generator terminals and check for leaks.
  8. Close generator main line circuit breaker; turn generator set off.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Battery charger must be connected to 120 VAC, 15 amp circuit
  • Record static gas pressure; must be as listed in Specifications

Full service-parts list: Generac QT 3.9L 40kW →, Generac QT Series →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.