Generac QT 1.6L 25kW — Engine Start-up and Transfer (Manual Transfer Switch)
Operation
For the Generac QT 1.6L 25kW, from the Generac owner's manual.
Applies to: Generac QT 1.6L 25kW, Generac In Line engine
Before you start
- Do not crank the engine continuously for longer than 30 seconds, or the heat may damage the starter motor.
- Transfer switch enclosure doors should be kept closed and locked. Extreme voltages are present.
Procedure
- Turn OFF or disconnect the utility power circuit to the transfer switch.
- Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.
- Set the standby generator's main line circuit breaker to its OFF (or OPEN) position.
- Start the generator.
- Let engine stabilize and warm up.
- Check all applicable instrument and gauge readings.
- Move the transfer switch manual handle to its STANDBY (GENERATOR) position.
- Set the standby generator's main line circuit breaker to its ON (or CLOSED) position. Load circuits are now powered by the standby generator.
Full service-parts list: Generac QT 1.6L 25kW →
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.