For the Generac Q-70G, from the Generac owner's manual.
Applies to: Generac GN-480 engine
Before you start
- DO NOT USE TAP WATER IN THE BATTERY.
- Damage may occur if the battery is connected incorrectly.
Procedure
- Check the tag on the engine for oil viscosity and classification; verify correct recommended oil is used, and drain and refill if necessary.
- Check the state of the battery; fill unsealed batteries with distilled water, recharge to 100 percent or replace if defective.
- Clean and wipe the entire generator.
- Reconnect the battery, observing battery polarity.
- Turn OFF all electrical loads. Add fuel if necessary and then start the engine.
- Allow the unit to warm up thoroughly.
- Apply electrical loads to at least 50 percent of the unit's rated wattage capacity.
- When the engine is thoroughly warmed up, shut it down.
Specs & values
- Load to at least 50 percent of rated wattage capacity
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.