Generac PRIMEPACT 50 — Out of Service Procedure - Return to Service

Maintenance · Generator

For the Generac PRIMEPACT 50, from the Generac owner's manual.

Applies to: Generac GN-410 engine

Before you start

  • Do not use tap water in the battery.
  • Damage may occur if the battery is connected incorrectly.

Procedure

  1. Check the tag on the engine for oil viscosity and classification; verify correct recommended oil is used.
  2. Check the state of the battery; fill all cells of unsealed batteries to the proper level with distilled water.
  3. Recharge the battery to 100 percent state of charge, or replace if defective.
  4. Clean and wipe the entire generator.
  5. Reconnect the battery observing battery polarity.
  6. Turn OFF all electrical loads, add fuel if necessary, then start the engine.
  7. Allow the unit to warm up thoroughly.
  8. Apply electrical loads to at least 50 percent of the unit's rated wattage capacity.
  9. When the engine is thoroughly warmed up, shut it down.

Specs & values

  • Recharge battery to 100 percent state of charge
  • Apply at least 50 percent rated wattage capacity