Home›Repair guides›Generac›Test 1 - Check Main Circuit Breaker

Generac PowerPact 5.6 kVA 50 Hz — Test 1 - Check Main Circuit Breaker

Testing & diagnosis · Main line circuit breaker

For the Generac PowerPact 5.6 kVA 50 Hz, from the Generac service manual.

Applies to: Generac PowerPact 5.6 kVA 50 Hz

Procedure

  1. Set VOM to R x 1 scale and zero the meter.
  2. With generator shut down, disconnect all wires from breaker terminals.
  3. Connect probes to Wire 11 (Blue) terminal and the E1 terminal.
  4. Set breaker Closed; VOM should read CONTINUITY.
  5. Set breaker Open; VOM should indicate INFINITY.
  6. Repeat with probes across Wire 44 (Black) and the E2 terminal.