Generac PowerPact 5.6 kVA 50 Hz — Select Automatic Operation

Operation · Controller and transfer switch

For the Generac PowerPact 5.6 kVA 50 Hz, from the Generac service manual.

Applies to: Generac PowerPact 5.6 kVA 50 Hz

Procedure

  1. Ensure transfer mechanism is in the Utility position.
  2. CLOSE the Utility source main line circuit breaker.
  3. Verify Utility voltage at terminals N1 and N2.
  4. Actuate the generator main line circuit breaker to Closed.
  5. Set the generator controller to the AUTO mode.

Full service-parts list: Generac PowerPact 5.6 kVA 50 Hz →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.