Generac PowerPact 5.6 kVA 50 Hz — Select Automatic Operation
Operation · Controller and transfer switch
For the Generac PowerPact 5.6 kVA 50 Hz, from the Generac service manual.
Applies to: Generac PowerPact 5.6 kVA 50 Hz
Procedure
- Ensure transfer mechanism is in the Utility position.
- CLOSE the Utility source main line circuit breaker.
- Verify Utility voltage at terminals N1 and N2.
- Actuate the generator main line circuit breaker to Closed.
- Set the generator controller to the AUTO mode.