Generac PowerPact 5.6 kVA 50 Hz — Retransfer to Utility and Manual Shutdown
Operation · Controller and transfer switch
For the Generac PowerPact 5.6 kVA 50 Hz, from the Generac service manual.
Applies to: Generac PowerPact 5.6 kVA 50 Hz
Procedure
- Set the generator MLCB to the OPEN position.
- Allow the generator to run at no-load several minutes to cool down.
- Set the generator controller to OFF mode.
- Locate a means of Utility disconnect and set it to OFF.
- Manually actuate the breaker in the transfer switch to Utility.
- Restore Utility voltage to the transfer switch.
- Set the generator controller to AUTO mode.
Full service-parts list: Generac PowerPact 5.6 kVA 50 Hz →
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.