Generac PowerPact 5.6 kVA 50 Hz — Retransfer to Utility and Manual Shutdown

Operation · Controller and transfer switch

For the Generac PowerPact 5.6 kVA 50 Hz, from the Generac service manual.

Applies to: Generac PowerPact 5.6 kVA 50 Hz

Procedure

  1. Set the generator MLCB to the OPEN position.
  2. Allow the generator to run at no-load several minutes to cool down.
  3. Set the generator controller to OFF mode.
  4. Locate a means of Utility disconnect and set it to OFF.
  5. Manually actuate the breaker in the transfer switch to Utility.
  6. Restore Utility voltage to the transfer switch.
  7. Set the generator controller to AUTO mode.

Full service-parts list: Generac PowerPact 5.6 kVA 50 Hz →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.