Home›Repair guides›Generac›Manual Start and Transfer to Standby

Generac PowerPact 5.6 kVA 50 Hz — Manual Start and Transfer to Standby

Operation · Controller and transfer switch

For the Generac PowerPact 5.6 kVA 50 Hz, from the Generac service manual.

Applies to: Generac PowerPact 5.6 kVA 50 Hz

Before you start

  • Engine will crank and start!

Procedure

  1. Set the controller switch to OFF mode.
  2. Set the generator main line circuit breaker to Open.
  3. Locate a means of Utility disconnect and set it to OFF.
  4. Manually actuate the breaker to Standby in the transfer switch.
  5. Set the controller switch to MANUAL mode; engine cranks and starts.
  6. Warm up 1-2 minutes; set the generator MLCB to Closed.

Full service-parts list: Generac PowerPact 5.6 kVA 50 Hz →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Generac repair guides →