Generac — Manually Starting the Unit

Operation · Generator set

From a Generac owner's manual covering: MDG150, MDG175, MDG250. Check it applies to your exact model before use.

Applies to: Generac MDG150, Generac MDG175, Generac MDG250, John Deere 6068HFG05 / 6068HFG06 engine

Before you start

  • Equipment damage. Do not attempt to start or operate a unit in need of repair or scheduled maintenance.

Procedure

  1. Set control power switch to ON (I).
  2. Display shows pre-start diagnosis; controller loads management software.
  3. Home screen appears; controller in STOP mode. Press AUTO/MANUAL button for MANUAL mode.
  4. Press green engine start (I) button to initiate startup.
  5. If engine fails to start it pauses 15 seconds, then makes two more attempts (three total).
  6. If it fails to start, fail-to-start alarm shows. Wait two minutes, press ENTER to clear alarm.
  7. Engine speeds up to a constant 1800 RPM.
  8. Check for excessive noise, vibration, and coolant, oil, or fuel leaks before loading.
  9. Verify the AC output voltage is correct.
  10. Verify frequency reads approximately 60 Hz with no loads connected.
  11. Switch main circuit breaker to ON (I), then add loads via their circuit breakers.

Specs & values

  • Operating speed 1800 RPM
  • Frequency approximately 60 Hz

Full service-parts list: Generac MDG150 →, Generac MDG175 →, Generac MDG250 →, John Deere 6068HFG05 / 6068HFG06 engine →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.