Generac — Manual Parallel Operation

Operation · Parallel system

From a Generac owner's manual covering: MDG150, MDG175, MDG250. Check it applies to your exact model before use.

Applies to: Generac MDG150, Generac MDG175, Generac MDG250

Before you start

  • Any crossed connections will prevent units from paralleling.

Procedure

  1. Verify the units to be paralleled are OFF.
  2. Secure all electrical connections to each unit and a common bus.
  3. Connect MSC cable(s) and terminating plugs (resistors) to the end units.
  4. Turn the battery disconnect ON.
  5. Turn on the controller power for each unit.
  6. Put the controller in MANUAL mode.
  7. Start each unit and allow them to warm up.
  8. Press the Close Circuit Breaker button on each unit.

Full service-parts list: Generac MDG150 →, Generac MDG175 →, Generac MDG250 →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.