From a Generac owner's manual covering: MDG150, MDG175, MDG250. Check it applies to your exact model before use.

Applies to: Generac MDG150, Generac MDG175, Generac MDG250, John Deere 6068HFG05 / 6068HFG06 engine

Before you start

  • Any crossed connections will prevent units from paralleling.

Procedure

  1. Verify units to be paralleled are OFF.
  2. Secure all electrical connections to each unit and a common bus; verify wiring is color coded or labeled.
  3. Connect MSC cable(s) and terminating plugs (resistors) to the end units.
  4. Turn the battery disconnect ON.
  5. Turn on the controller power for each unit.
  6. Put the controller in MANUAL mode.
  7. Start each unit and allow them to warm up.
  8. Press the Close Circuit Breaker button on each unit.

Full service-parts list: Generac MDG150 →, Generac MDG175 →, Generac MDG250 →, John Deere 6068HFG05 / 6068HFG06 engine →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.