Generac GT-990 — Generator Tests Under Load

Testing & diagnosis

For the Generac GT-990, from the Generac owner's manual.

Applies to: Generac GT-990 engine

Before you start

  • Proceed with caution; generator power voltage is supplied to the transfer switch.

Procedure

  1. Set main circuit breaker to OFF and turn OFF all loads at T1 and T2.
  2. Set AUTO/OFF/MANUAL switch to OFF and turn OFF utility power to transfer switch.
  3. Manually set transfer switch to the STANDBY position.
  4. Set AUTO/OFF/MANUAL switch to MANUAL; engine cranks and starts.
  5. Let the engine stabilize and warm up for a few minutes.
  6. Set main circuit breaker to ON; loads are powered by the generator.
  7. Turn ON electrical loads equal to full rated capacity.
  8. Check E1-E2 voltage greater than 230 volts and frequency greater than 58 Hertz.
  9. Run at full rated load for 20-30 minutes, listening for unusual noise and checking for oil leaks.
  10. Turn OFF electrical loads and set main circuit breaker to OFF.
  11. Let engine run at no-load for a few minutes then set switch to OFF.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Voltage should be greater than 230 volts
  • Frequency should be greater than 58 Hertz

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.