Procedure

  1. Strip insulation off wire ends.
  2. Loosen lugs at neutral, ground, and power wire (mains) terminals.
  3. Connect ground wire to ground lug and tighten to spec.
  4. Connect neutral wire to neutral lug, if applicable; tighten to spec.
  5. Insert power wires into corresponding lugs and tighten to spec.
  6. Verify factory-installed ground array and neutral connections tightened to 25 in-lbs.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Power wire terminals 120 in-lbs (13.56 Nm)
  • Ground stud nut 35 in-lbs (3.95 Nm)

Full service-parts list: Generac G0072100 →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.