Home›Repair guides›Generac›Generator Tests Under Load

Generac G0072100 — Generator Tests Under Load

Testing & diagnosis

For the Generac G0072100, from the Generac service manual.

Applies to: Generac G0072100

Before you start

  • Do not manually transfer under load.

Procedure

  1. Verify generator in OFF mode and set MLCB to OFF (OPEN).
  2. Turn off all breakers/loads.
  3. Turn off utility power to transfer switch.
  4. Manually set transfer switch to STANDBY (load to E1/E2).
  5. Press MANUAL button to start engine; record cranking fuel pressure.
  6. Warm up, record running fuel pressure.
  7. Set MLCB to ON (CLOSED); turn on loads one by one.
  8. Verify approximately 240 volts and 60 Hz.
  9. Run at full rated load 20–30 minutes; inspect for leaks/overheating.
  10. Record loaded fuel pressure.
  11. Turn off loads and set MLCB to OFF.
  12. Run at no-load 2–5 minutes; press OFF.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 240 volts approximately
  • 60 Hz approximately
  • full rated load run 20–30 minutes

Full service-parts list: Generac G0072100 →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.