Generac — Forcing a Manual Exhaust After-Treatment Cleaning

Operation · SCR / after-treatment system

From a Generac owner's manual covering: MDG150, MDG175, MDG250. Check it applies to your exact model before use.

Applies to: Generac MDG150, Generac MDG175, Generac MDG250, John Deere 6068HFG05 / 6068HFG06 engine

Before you start

  • Always park the unit in a safe location for elevated exhaust temperatures and check for adequate fuel level before starting cleaning.
  • Risk of Burn. Stay clear of the exhaust system during operation and exhaust filter cleaning.

Procedure

  1. Open the control door and locate the switch labeled REGEN INHIBIT.
  2. Set and hold the switch in ON/FORCED (I) for five seconds.
  3. Enter the SCR status screen and verify the regeneration indicator appears above SCR LAMP - SOLID.

Specs & values

  • Cleaning cycle duration approximately 45 minutes

Full service-parts list: Generac MDG150 →, Generac MDG175 →, Generac MDG250 →, John Deere 6068HFG05 / 6068HFG06 engine →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.