Home›Repair guides›Generac›Engine Start-up and Transfer (Manual Transfer Switch)

Generac — Engine Start-up and Transfer (Manual Transfer Switch)

Operation · Generator and manual transfer switch

From a Generac owner's manual — check it applies to your exact model before use.

Applies to: Generac In Line engine

Before you start

  • The Maintenance Disconnect Switch and AUTO/OFF/MANUAL switches must be set properly, or the generator will crank and start as soon as utility power is turned off.
  • Do not attempt manual operation until all power supplies to the transfer switch have been positively turned off, or lethal electrical shock will result.
  • Do not crank the engine continuously for longer than 30 seconds, or the heat may damage the starter motor.

Procedure

  1. Turn OFF or disconnect the utility power circuit to the transfer switch.
  2. Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.
  3. Set the standby generator's main line circuit breaker to its OFF (or OPEN) position.
  4. Start the generator.
  5. Let engine stabilize and warm up.
  6. Check all applicable instrument and gauge readings.
  7. Move the transfer switch manual handle to its STANDBY (GENERATOR) position.
  8. Set the standby generator's main line circuit breaker to its ON (or CLOSED) position.

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Generac repair guides →