Home›Repair guides›Generac›Automatic Parallel

Generac — Automatic Parallel

Operation · Paralleled gensets

From a Generac owner's manual covering: MDG150, MDG175, MDG250. Check it applies to your exact model before use.

Applies to: Generac MDG150, Generac MDG175, Generac MDG250, John Deere 6068HFG05 / 6068HFG06 engine

Procedure

  1. Verify the units to be paralleled are OFF.
  2. Secure all electrical connections to each unit and a common bus; verify wiring is properly color coded or labeled.
  3. Connect MSC cable(s) and terminating plugs (resistors) to the end units.
  4. Turn the battery disconnect ON.
  5. Connect two wire start signal (dry contact closure) to all generators on the MSC network.
  6. Turn ON the controller power for each unit.
  7. Put the controller in AUTO mode.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Generac MDG150 →, Generac MDG175 →, Generac MDG250 →, John Deere 6068HFG05 / 6068HFG06 engine →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.