Generac 4700 / QuietPact 40 — Stator Short-to-Ground Insulation Test

Testing & diagnosis

For the Generac 4700 / QuietPact 40, from the Generac service manual.

Applies to: Generac 4700, Generac QuietPact 40, Generac GH-220 engine

Before you start

  • Insulation resistance testers such as hi-pot testers and megohmmeters are a source of high and dangerous electrical voltage.
  • Do not connect tester leads to any leads routed into the generator control panel.

Procedure

  1. Disconnect and isolate all Stator leads (11S, 22S, 11P, 22P, 33, 44, 2, 6, 55, 66, 77).
  2. Connect the terminal ends of all Stator leads together.
  3. Connect tester leads across all Stator leads and to frame ground on the Stator can.
  4. Apply a voltage of 1500 volts. Do NOT apply voltage longer than one (1) second.
  5. If insulation breakdown is indicated, clean and dry the Stator and re-test; replace Stator if it fails the second test.

Tools required

  • Hi-pot tester or megohmmeter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 1500 volts applied
  • Do not exceed 1 second

Full service-parts list: Generac 4700 →, Generac QuietPact 40 →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.