Generac 005336-0 / 005337-0 — Engine Start-up and Transfer (Manual Transfer Switch)
Operation · Manual transfer switch / generator
For the Generac 005336-0 / 005337-0, from the Generac owner's manual.
Applies to: Generac In Line engine
Before you start
- Do not crank the engine continuously for longer than 30 seconds.
- Do not attempt manual operation until all power supplies to the transfer switch have been positively turned off.
- Transfer switch enclosure doors should be kept closed and locked.
Procedure
- Turn OFF or disconnect the utility power circuit to the transfer switch.
- Set the transfer handle to its UTILITY (NORMAL) position.
- Set the standby generator's main line circuit breaker to OFF (OPEN).
- Start the generator.
- Let engine stabilize and warm up and check all instrument and gauge readings.
- Move the transfer switch manual handle to its STANDBY (GENERATOR) position.
- Set the standby generator's main line circuit breaker to ON (CLOSED).
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.