Generac 005213-0 — Engine Start-up and Transfer (Manual Transfer Switch)
Operation · Transfer switch / generator
For the Generac 005213-0, from the Generac owner's manual.
Applies to: Generac In Line engine
Before you start
- Do not crank the engine continuously for longer than 30 seconds, or the heat may damage the starter motor.
Procedure
- Turn OFF or disconnect the utility power circuit to the transfer switch.
- Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to utility.
- Set the standby generator's main line circuit breaker to its OFF (or OPEN) position.
- Start the generator.
- Let engine stabilize and warm up.
- Check all instrument and gauge readings; when correct, move the transfer switch manual handle to STANDBY (GENERATOR).
- Set the standby generator's main line circuit breaker to its ON (or CLOSED) position.
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.