Fischer Panda PMS 4200 FCB / Panda PMS 4200 FCB — Starting Generator

Operation

For the Fischer Panda PMS 4200 FCB / Panda PMS 4200 FCB, from the Fischer Panda operator's manual.

Applies to: Fischer Panda Panda PMS 4200 FCB, Farymann 18W430 engine

Before you start

  • Do not start generator with load connected.

Procedure

  1. If necessary, open fuel valve.
  2. If necessary, close main battery switch.
  3. Check that all load is switched off.
  4. Press ON button; Power control light must light up.
  5. Press START button; starter max 20 seconds, then pause at least 60 seconds.
  6. Check voltmeter for AC voltage and frequency within tolerance.
  7. Switch on load only when voltage is within permissible range; connect loads step by step.

Specs & values

  • AC voltage tolerance ±3 V without load at nominal voltage
  • Generator frequency should be 4% below nominal when running without load