Denyo — Generator Shutdown Procedure

For these Denyo models: DCA-220ESM, DF-2400M.

Applies to: Denyo DCA-220ESM, Denyo DF-2400M

Before you start

  • For emergency stop, keep pushing the EMERGENCY STOP button until the engine stops. This button is a push-locked type and the contact is released in case of rotating it to clock direction. The engine does not re-start unless the contact is released.

Procedure

  1. Turn OFF the circuit breaker of the load.
  2. Turn OFF the circuit breaker of the machine.
  3. Turn the speed change-over switch to LOW position and put the machine in cooling operation for a few minutes.
  4. Set the starter switch in STOP position. The engine will stop immediately.
  5. Remove the key from the starter switch and keep it at hand.
  6. Check the amount of fuel. Supply fuel if necessary.
  7. Check for leakage of oil, fuel and water.
  8. Check that the panel light goes out.

Source: manual:DCA-220ESM.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.