Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 176 kW |
| Standby kVA | 200 |
| Oil capacity | 37.0 L |
| Voltage options | 190 V, 220 V |
| Phase | three-phase (four wire) |
| Rated current | 820 A |
| Power factor | 0.8 |
| Coolant capacity | 45 L |
| Dimensions (L×W×H) | 3700×1300×1750 mm |
| Dry weight | 3670 kg |
| Fuel tank | 380.0 L |
Engine
| Displacement | 11.945 L |
|---|---|
| Aspiration | direct injection with turbocharger (AC: aftercooler) |
| Rated speed | 1500 rpm |
Maintenance & consumables
for the Mitsubishi 6D24-TCE2| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | 60A6101300 | PartsGeek | |||
| Fuel filter | 3436204100 | PartsGeek | |||
| Oil filter | 3254001600 | PartsGeek | |||
| Belt | — | 1000 hr | find | ||
| Coolant | 42.0 L | — | 1000 hr | ||
| Coolant filter | — | find | |||
| Oil | 37.0 | — | 290 hr |
Common questions
What is the power rating of the Denyo DF-2400M?
The Denyo DF-2400M is rated 176 kW standby (200.0 kVA).
What engine does the Denyo DF-2400M use?
The Denyo DF-2400M is powered by the Mitsubishi 6D24-TCE2 engine.
What fuel does the Denyo DF-2400M use?
The Denyo DF-2400M runs on Diesel.
Troubleshooting
24Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Cell motor will not run | Repair | |
| Engine will not start up | Turn ON | |
| Cell motor runs | Speed will not rise | |
| Engine starts up | Speed rises | |
| Voltmeter will not operate | Rated voltage will not be reached | |
| Voltage goes too high | Applied load causes large voltage drop | |
| Discharged Battery | Charge or replace | |
| Low speed | Voltmeter failure | |
| Unbalanced Joad | Balance | |
| Cell motor detached, loosened, or corroded | Repair will not run battery terminal | |
| Engine will not start up or revolution is low | Improper starter switch Replace | |
| Fuel shortage | Supply | |
| Blinded fuel filter | Replace element | |
| Air in fuel system | Remove | |
| Speed will not rise | Air in fuel system Remove Blinded fuel filter Replace element | |
| Compression failure | Repair engine | |
| Blinded air cleaner | Replace element | |
| Engine stop by oil failure | Oil shortage Supply Oil pressure switch failure Replace Blinded oil filter Replace element | |
| Cooling water shortage | Supply | |
| Over heat (water temperature) | Fan belt looseness Adjust Blinded core of radiator Clean | |
| Engine thermostat failure | Repair | |
| Voltmeter failure | Replace | |
| AVR failure | Contact distributor or our office | |
| Rated voltage will not be reached | Burned rotary rectifier Contact our office Burned generator wiring Contact our office VR failure Contact distributor or our office |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | |||
| Standby |
Available documents
Spec sheet — DCA-220SPK3, DCA-300SPK3 (Denyo)Service manual — DCA-220ESM (Denyo)