Cummins/Onan — Voltage Setpoint Adjustment
Adjustments · PCC1302 control
From a Cummins/Onan service manual covering: 1302 series control, HMI211, HMI211RS, PCC 1302. Check it applies to your exact model before use.
Applies to: Cummins/Onan PCC 1302
Procedure
- Connect to the control with your PC based service tool.
- Verify the nominal voltage trim is set to the desired value.
- With the genset OFF, attach a calibrated Voltmeter to the AC Output from L1 to L2.
- Start the genset and allow it to reach normal operating speed.
- Adjust the trim Voltage Adjust to move the voltage Setpoint either positive or negative per your requirement.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Full service-parts list: Cummins/Onan PCC 1302 →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.