Cummins/Onan — Voltage Measurement for Regulation (Regulation Calibration)

Adjustments · PCC1302 control

From a Cummins/Onan service manual covering: 1302 series control, HMI211, HMI211RS, PCC 1302. Check it applies to your exact model before use.

Applies to: Cummins/Onan PCC 1302

Procedure

  1. View the Service Menu by holding down the "up" and "down" arrow keys on any of the operator menus.
  2. Select item 1, "Setup Menus".
  3. Enter setup menu password 574.
  4. Select item 1, "Genset Service".
  5. Select item 1, and verify the "Volts AC" setting is correct for your application; adjust and save if necessary.
  6. Press the back button to return to the service menu.
  7. Select item 3, "Meter Calib."
  8. Press the "Adjust" button and change the "Reg Volt Adj:" value. The effect of this trim is inverse on the regulated voltage.
  9. Save the adjustments by pressing the "Save" button.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan PCC 1302 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.