Cummins/Onan — Voltage Measurement for Display (Meter Calibration)

Adjustments · PCC1302 control

From a Cummins/Onan service manual covering: 1302 series control, HMI211, HMI211RS, PCC 1302. Check it applies to your exact model before use.

Applies to: Cummins/Onan PCC 1302

Before you start

  • Contacting high voltage components can cause electrocution, resulting in severe personal injury or death. Calibration and adjustment must be performed by technically qualified personnel only.

Procedure

  1. View the service menu by holding down the "up" and "down" arrow keys on any of the operating menus.
  2. Select item 1, "Setup Menu".
  3. Enter Setup menu password "574".
  4. Select item 1, "Genset Service".
  5. Select item 1, and verify the "Volts AC" setting is correct for your application; adjust and save if necessary.
  6. Press the back button to return to service menu.
  7. With the genset OFF, attach a calibrated voltmeter to the AC Output from L1 to L2.
  8. Start the genset and allow it to reach normal operating speed.
  9. Select item 3, "Meter Calib".
  10. Press the down arrow twice to scroll down to the "Metering Voltage Adjust".
  11. Adjust the three parameters one by one so the display agrees with the calibrated voltmeter.
  12. Shut the generator set OFF.
  13. Repeat for L2 and L3.
  14. Save the adjustment by pressing the "Save" button.

Tools required

  • Calibrated voltmeter Amazon
  • PC based service tool (optional) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan PCC 1302 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →