Home›Repair guides›Cummins/Onan›Voltage Adjustment (Standard Regulator)

Cummins/Onan — Voltage Adjustment (Standard Regulator)

Adjustments · Voltage regulator VR21

From a Cummins/Onan service manual covering: DL4, DL6, DL6T, DL6U. Check it applies to your exact model before use.

Applies to: Cummins/Onan DL4, Cummins/Onan DL6, Cummins/Onan DL6T

Procedure

  1. Center the panel mounted voltage adjustment knob with pointer vertical.
  2. Start the set and allow it to stabilize at correct frequency and speed.
  3. Turn R18 counterclockwise to decrease voltage or clockwise to increase.
  4. Set voltage with no load connected (e.g., 246 volts for 120/240).
  5. Turn R26 counterclockwise until unstable, then clockwise until voltage stabilizes.

Specs & values

  • Set no-load voltage for 246 volts on a 120/240-volt connection

Full service-parts list: Cummins/Onan DL6 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →