Home›Repair guides›Cummins/Onan›Vents and Ducts

Cummins/Onan — Vents and Ducts

Installation · Ventilation

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFEJ, Cummins/Onan DFEK, Cummins/Onan QSX15-G9 engine

Procedure

  1. For indoor installations, locate vents so incoming air passes through the immediate area of the installation before exhausting; install the air outlet higher than the air inlet.
  2. Size the vents and ducts large enough to allow the required flow rate of air.
  3. Locate the outlet vent so the effects of wind are eliminated, or install a wind barrier.

Specs & values

  • The free area of ducts must be as large as the exposed area of the radiator

Full service-parts list: Cummins/Onan DFEJ →, Cummins/Onan DFEK →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.