Cummins/Onan — Testing Field Windings for Grounds

Testing & diagnosis

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan MCCK

Procedure

  1. Disconnect all field leads before testing.
  2. Touch one test prod to F1 (+) and the other prod to the frame.
  3. The buzzer should not sound or the lamp should not light.
  4. If the tester buzzes or lights, the field is grounded and must be replaced.
  5. Test lead F2 (-) in the same manner.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan MCCK →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.