Cummins/Onan — Stopping at the Operator Panel (Manual Mode)

Operation · PowerCommand 2.3 control

From a Cummins/Onan operator's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFEJ, Cummins/Onan DFEK, Cummins/Onan QSX15-G9 engine

Before you start

  • Hot shutdown under load should be avoided to prolong reliability; it results in a Hot Shutdown Warning.
  • Pressing the Stop button twice stops the set immediately without a cool down run.

Procedure

  1. Remove the load.
  2. Open the main circuit breaker.
  3. Press the Stop button on the HMI operator panel.
  4. This initiates the generator set cool down run; the countdown timer is displayed.
  5. Once the cool down timer expires, the generator set shuts off and enters Off mode.

Full service-parts list: Cummins/Onan DFEJ →, Cummins/Onan DFEK →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.