Home›Repair guides›Cummins/Onan›Starting at Remote (Meter) Panel

Cummins/Onan — Starting at Remote (Meter) Panel

Operation · Generator set

From a Cummins/Onan operator's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan MDKUB, Cummins/Onan MDKWB, Kubota Z482B engine, Kubota D722B engine

Procedure

  1. Monitor oil pressure, water temperature, and DC voltage while starting and after about one minute of run.
  2. Oil pressure should be 28 to 64 psi (294 to 543 kPa) at operating temperature.
  3. Coolant temperature should be 165° to 195° F (74° to 91° C).
  4. DC voltmeter should read 12.5 to 15 volts.

Specs & values

  • Oil pressure 28 to 64 psi (294 to 543 kPa)
  • Coolant temperature 165° to 195° F (74° to 91° C)
  • DC voltage 12.5 to 15 volts

Full service-parts list: Cummins/Onan MDKUB →, Cummins/Onan MDKWB →, Kubota Z482B engine →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.