Cummins/Onan — Returning the Genset to Service

Operation · Generator set

From a Cummins/Onan operator's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan MDKUB, Cummins/Onan MDKWB, Kubota Z482B engine, Kubota D722B engine

Before you start

  • Battery electrolyte can cause severe eye damage and burns.

Procedure

  1. Remove plug from exhaust outlet and open sea cock.
  2. Check tag on oil base and verify oil viscosity is correct for existing ambient temperature.
  3. Clean and check battery. Measure electrolyte specific gravity (1.260 @ 80°F [27°C]) and verify proper level. Charge if low.
  4. Prime fuel system.
  5. Connect starting battery, negative cable last.
  6. Remove all loads before starting genset.
  7. After starting, run generator set at no load for roughly 30 seconds. Then apply load of at least 50 percent rated capacity.
  8. Check all gauges for normal readings.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Specific gravity 1.260 @ 80°F (27°C)
  • Apply at least 50 percent rated capacity

Full service-parts list: Cummins/Onan MDKUB →, Cummins/Onan MDKWB →, Kubota Z482B engine →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.