Cummins/Onan — Returning Set to Service
Maintenance · Generator set
From a Cummins/Onan operator's manual — check it applies to your exact model before use.
Applies to: Cummins/Onan GGHG, Cummins/Onan GGHH, Cummins/Onan V-10 WSG-1068 engine
Procedure
- Remove protective cover.
- Remove exhaust plugs, seal from carburetor and PVC hose, and replace air cleaner.
- Check oil dipstick to make sure crankcase is full.
- Refill cooling system.
- Reconnect battery (positive cable first) and check specific gravity.
- Connect the battery charger (if applicable).
- Connect engine coolant heater to power supply (if applicable).
- Remove all loads before starting set.
- Start set and apply load of at least 50% of nameplate rating.
- Check all gauges for normal readings. Set is now ready for service.
Specs & values
- Apply load of at least 50% of nameplate rating
Full service-parts list: Cummins/Onan GGHG →, Cummins/Onan GGHH →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.