Home›Repair guides›Cummins/Onan›Resetting the Emergency Stop (PCC front panel)

Cummins/Onan — Resetting the Emergency Stop (PCC front panel)

Operation · PowerCommand Control 3100

From a Cummins/Onan operator's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DQAD, Cummins/Onan DQAE, Cummins/Onan DQAF, Cummins/Onan QSM11 engine

Before you start

  • Accidental starting of the generator set can cause severe personal injury or death.

Procedure

  1. Pull the button out.
  2. Move the Run/Off/Auto switch to Off.
  3. Press the front panel Reset switch.
  4. Select Run or Auto, as required.

Specs & values

  • Emergency Stop shutdown status (Code 102) can be reset only at the PCC front panel

Full service-parts list: Cummins/Onan DQAD →, Cummins/Onan DQAE →, Cummins/Onan DQAF →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.