Home›Repair guides›Cummins/Onan›Reset After Codes 1433 / 1434 (Emergency Stop)

Cummins/Onan — Reset After Codes 1433 / 1434 (Emergency Stop)

Operation · Emergency stop circuit

From a Cummins/Onan operator's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFEJ, Cummins/Onan DFEK, Cummins/Onan QSX15-G9 engine

Before you start

  • Do not use the Emergency Stop button for a normal shut-down; it prevents a cooling down run.
  • Investigate and remedy the cause before fault reset and generator set start.

Procedure

  1. Pull, or twist and pull the button out.
  2. Press the Stop button on the operator panel to acknowledge this action.
  3. Press the Reset button.
  4. Press the Auto or Manual Run button as previously determined.

Full service-parts list: Cummins/Onan DFEJ →, Cummins/Onan DFEK →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.