Home›Repair guides›Cummins/Onan›Testing the PMG

Cummins/Onan QST30 — Testing the PMG

Testing & diagnosis

For the Cummins/Onan QST30, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DFHA, Cummins/Onan DFHB, Cummins/Onan DFHC, Cummins/Onan DFHD, Cummins/Onan QST30, Cummins/Onan QST30 engine

Before you start

  • HAZARDOUS VOLTAGE. Use insulated tools and dry insulating mat.

Procedure

  1. Disconnect plug J10 from voltage regulator output stage module.
  2. Start engine and let speed stabilize.
  3. Measure voltage across J10-1 & J10-4, J10-4 & J10-5, J10-5 & J10-1. Should be at least 150 VAC for 50 Hz, 180 VAC for 60 Hz.
  4. Stop set and measure resistance across same lead pairs. Should be 2.6 ±10% ohms for P7 and HC6.

Tools required

  • Wheatstone bridge or digital ohmmeter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • PMG voltage at least 150 VAC for 50 Hz sets
  • PMG voltage at least 180 VAC for 60 Hz sets
  • PMG resistance 2.6 ±10% ohms for P7 and HC6

Full service-parts list: Cummins/Onan DFHA →, Cummins/Onan DFHB →, Cummins/Onan DFHC →, Cummins/Onan DFHD →, Cummins/Onan QST30 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.