Before you start

  • Voltage must begin at zero volts and be gradually increased.
  • Monitor current to prevent exceeding alternator rating.

Procedure

  1. Bolt alternator three phase output terminals together.
  2. Remove accessory box cover and remove plug P10 from J10 of voltage regulator output module.
  3. Connect positive lead to P10-6 red wire (X), negative to P10-3 brown wire (XX).
  4. Attach clamp-on ammeter to alternator leads. Adjust 12 VDC source for zero voltage.
  5. Start set and very slowly increase excitation voltage to highest current without exceeding rating.
  6. Run generator set approximately one hour, then repeat insulation resistance tests.