Cummins/Onan QST30 — Digital Voltage Display Calibration

Adjustments · PCC digital display

For the Cummins/Onan QST30, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DFHA, Cummins/Onan DFHB, Cummins/Onan DFHC, Cummins/Onan DFHD, Cummins/Onan QST30, Cummins/Onan QST30 engine

Procedure

  1. Select >> from Main Menu, proceed to VOLTS L12 menu.
  2. With generator set OFF, attach calibrated frequency/voltmeter to AC output L1 to L2.
  3. Start generator set and allow to reach normal operating speed.
  4. Calibrate VOLTS L12 reading to agree with calibrated voltmeter.
  5. Shut generator set OFF.
  6. Repeat steps 10 through 13 for L23 and L31.
  7. Select EXIT if no calibration; SAVE then EXIT if calibration made.

Tools required

  • calibrated frequency/voltmeter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan DFHA →, Cummins/Onan DFHB →, Cummins/Onan DFHC →, Cummins/Onan DFHD →, Cummins/Onan QST30 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.