Cummins/Onan QST30 — Digital Ammeter Display Calibration

Adjustments · PCC digital display

For the Cummins/Onan QST30, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DFHA, Cummins/Onan DFHB, Cummins/Onan DFHC, Cummins/Onan DFHD, Cummins/Onan QST30, Cummins/Onan QST30 engine

Procedure

  1. Select >> from Main Menu, proceed to AMPS L1 menu.
  2. With generator set OFF, attach calibrated ammeter to L1.
  3. Start generator set and allow to reach normal operating speed.
  4. Load generator set to maximum rated kVA at rated voltage.
  5. Calibrate AMPS L1 reading to agree with calibrated ammeter.
  6. Repeat steps 17 through 20 for L2 and L3.
  7. Select EXIT if no calibration; SAVE then EXIT if calibration made.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan DFHA →, Cummins/Onan DFHB →, Cummins/Onan DFHC →, Cummins/Onan DFHD →, Cummins/Onan QST30 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.