Before you start

  • Attach a warning to refill oil before operation.

Procedure

  1. Run the plant until thoroughly warmed up.
  2. Drain the oil from the oil base while still warm; attach a warning to refill before operation.
  3. Drain water if it will freeze.
  4. Clean the air cleaner.
  5. Lubricate the governor linkage.
  6. Protect against dust by wrapping with a clean cloth.
  7. Plug the exhaust outlet to prevent entrance of moisture or dirt.
  8. Wipe generator brushes, slip rings, etc. clean; do not use lubricant or preservative.
  9. Wipe the entire unit clean and coat parts likely to rust with a light film of grease or oil.
  10. Provide a suitable cover for the entire unit.
  11. Disconnect battery and follow standard battery storage procedure.