Operation

From a Cummins/Onan service manual covering: ES2075s, FS1870s, M11979s, M1976s, M1977s, M1978s. Check it applies to your exact model before use.

Applies to: Kubota 2482B engine

Before you start

  • Do not use ether or any starting fluid as a starting aid; it can cause an explosion.
  • Do not engage the starter longer than 10 seconds; wait 30 seconds between starting attempts.

Procedure

  1. Put the Heat/Off/AC switch in the center Off position.
  2. Press the Start/Stop switch to Start and release it when the engine starts.
  3. If the engine does not start after cranking 10 seconds, release the switch, wait 30 seconds and try again.
  4. If the engine still does not start, hold the Preheat switch and Start switch in at the same time.
  5. If the engine does not start on the third try, check the fuel supply, fuel system priming and oil level.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.