Cummins/Onan — PCC Power On/Standby Mode Selection
Operation · PowerCommand 3100 Control
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan DQAD, Cummins/Onan DQAE, Cummins/Onan DQAF, Cummins/Onan QSM11 engine
Procedure
- Remove the negative (−) battery cable(s) from the generator set starting battery as follows: move the Run/Off/Auto switch to OFF; press the Emergency Stop button and wait at least 30 seconds; turn off
- Set the Power On / Standby Mode switch (S5 in Figure 8-1) to the desired position.
- Power On Mode: slide the switch to the left. The PCC initializes the operating software and permits operation of the menu display panel.
- Standby Mode: slide the switch to the right. The PCC operating software will be initiated by moving the Run/Off/Auto switch to Run, pressing the Self Test button, a remote start input signal (genset i
Specs & values
- Power On Mode: switch S5 left
- Standby Mode: switch S5 right
- Software timer shuts down power after 30 seconds if no menu selections are made
Full service-parts list: Cummins/Onan DQAD →, Cummins/Onan DQAE →, Cummins/Onan DQAF →