Cummins/Onan PCC 3100 — External Emergency Stop Reset

Operation · Emergency stop switch

For the Cummins/Onan PCC 3100, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan DFHA, Cummins/Onan DFHB, Cummins/Onan DFHC, Cummins/Onan DFHD, Cummins/Onan PCC 3100, Cummins/Onan QST30 engine

Before you start

  • Emergency Stop shutdown can be reset only at the generator set control panel.

Procedure

  1. Pull the button (external) and allow it to pop out.
  2. Turn the O/Manual/Auto switch to O (Off).
  3. Press the front panel Fault Acknowledge/Reset button.
  4. Select Manual or Auto, as required.

Full service-parts list: Cummins/Onan DFHA →, Cummins/Onan DFHB →, Cummins/Onan DFHC →, Cummins/Onan DFHD →, Cummins/Onan PCC 3100 →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.