Cummins/Onan P4500iDF — Parallel Operation

Operation · parallel kit

For the Cummins/Onan P4500iDF, from the Cummins/Onan owner's manual.

Applies to: Cummins/Onan P4500iDF

Before you start

  • NEVER connect or disconnect the parallel cord leads when a generator is running.
  • DO NOT connect two red leads or two black leads into the same generator.

Procedure

  1. Make sure both generator battery switches and ECO MODE switches are OFF.
  2. Connect black and red parallel cable leads to the black ports on each control panel.
  3. Connect the green ground lead to the ground terminal on each generator and tighten the nut.
  4. Start one generator and wait until the OUTPUT READY LED illuminates.
  5. Start the second generator and wait until the OUTPUT READY LED illuminates.
  6. Connect additional loads as described in Power Management.
  7. Unplug all loads before stopping the generators.

Full service-parts list: Cummins/Onan P4500iDF →

Source: Cummins/Onan owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.