Home›Repair guides›Cummins/Onan›Out-of-Service Protection (over 30 days)

Cummins/Onan — Out-of-Service Protection (over 30 days)

Maintenance · Generating set

From a Cummins/Onan operator's manual covering: 40.0DDB-515R, 50.0DDB-15R, 50.0DDB-9XR. Check it applies to your exact model before use.

Applies to: Cummins/Onan 40.0DDB-515R, Cummins/Onan 50.0DDB-15R, Cummins/Onan 50.0DDB-9XR, John Deere 6329D engine, John Deere 6329D (300-6329D) engine

Procedure

  1. Run set until thoroughly warm.
  2. Drain oil from oil base while still warm; refill and attach warning tag stating oil viscosity used.
  3. Remove each injector; pour 1 ounce (two tablespoons) rust inhibitor or SAE #10 oil into each cylinder.
  4. Crank engine over several times; install injectors.
  5. Service air cleaner.
  6. Clean throttle linkage and protect with a clean cloth.
  7. Plug exhaust outlets to prevent moisture, bugs and dirt.
  8. Wipe entire unit; coat rust-susceptible parts with light film of grease or oil.
  9. Disconnect battery and follow standard battery storage procedure.
  10. Provide a suitable cover for the entire unit.

Full service-parts list: Cummins/Onan 40.0DDB-515R →, Cummins/Onan 50.0DDB-15R →, Cummins/Onan 50.0DDB-9XR →, John Deere 6329D engine →, John Deere 6329D (300-6329D) engine →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →